Study on Steep Front Impulse Test Voltage Value of Disc Insulators with Variation in the Number of Units of Insulator String


Affiliations
1 High Voltage Division, CPRI, Bangalore - 560080, Karnataka, India
     

   Subscribe/Renew Journal


The insulators used in power transmission and distribution networks should withstand abnormal system-generated switching impulses and natural lightning impulses. To avoid the failure of insulators in the field, the impulse puncture strength evaluation of the ceramic insulators is important. IEC 61211 standard stipulates the procedure to evaluate the ceramic disc insulators’ strength to withstand steep front impulses. In this test, the test voltage is determined by using a short standard string of five insulators. This paper presents the variation in the impulse stresses across the disc insulator units in the string due to non-linear voltage distribution under impulse flashover. This paper also correlates the test voltage values defined by the IEC standard with the highest stress on insulator units under impulse flashover of string insulators by using voltage distribution. The correlation study has been carried out with insulator strings having different arcing distances by using a different number of units.

Keywords

Cap and Pin Insulator, Lightning Critical Flashover Voltage, Test Voltage (2.8pu), V-t Characteristics, Voltage Distribution.
User
Subscription Login to verify subscription
Notifications
Font Size


  • Study on Steep Front Impulse Test Voltage Value of Disc Insulators with Variation in the Number of Units of Insulator String

Abstract Views: 361  |  PDF Views: 0

Authors

K. Marimuthu
High Voltage Division, CPRI, Bangalore - 560080, Karnataka, India
Y. Dharmesh
High Voltage Division, CPRI, Bangalore - 560080, Karnataka, India
G. Pandian
High Voltage Division, CPRI, Bangalore - 560080, Karnataka, India

Abstract


The insulators used in power transmission and distribution networks should withstand abnormal system-generated switching impulses and natural lightning impulses. To avoid the failure of insulators in the field, the impulse puncture strength evaluation of the ceramic insulators is important. IEC 61211 standard stipulates the procedure to evaluate the ceramic disc insulators’ strength to withstand steep front impulses. In this test, the test voltage is determined by using a short standard string of five insulators. This paper presents the variation in the impulse stresses across the disc insulator units in the string due to non-linear voltage distribution under impulse flashover. This paper also correlates the test voltage values defined by the IEC standard with the highest stress on insulator units under impulse flashover of string insulators by using voltage distribution. The correlation study has been carried out with insulator strings having different arcing distances by using a different number of units.

Keywords


Cap and Pin Insulator, Lightning Critical Flashover Voltage, Test Voltage (2.8pu), V-t Characteristics, Voltage Distribution.

References





DOI: https://doi.org/10.33686/prj.v18i2.222175